0113 248 9966
0113 248 9966
Booking and info

Kewtech EZYPAT PAT Tester

Kewtech Official Distributor
  • Test Class I and Class II appliances alongside IEC leads
  • Insulation testing and two different voltages plus 5s continuity test
  • Screen flashes green for PASS result and red for FAIL

Optional Extras

£339.00+VAT
In stock
+

Product videos

Description

The Kewtech EZYPAT PAT Tester allows the user to carry out 200mA continuity testing, insulation resistance testing, substitute leakage measurement and polarity testing. Continuity testing on Class I appliances and extension leads can be set as a quick test or a five-second test whilst a 250V test voltage for insulation allows resting on surge-protected extension leads. Accuracy is aided by a nulling function for test lead resistance.

The backlit digital display on the Kewtech EZYPAT glows red or green to indicate a PASS or FAIL alongside showing actual readings and results for each test. Separate automatic testing sequences for Class I appliances, Class II appliances and extension leads can each be initiated by pressing a clearly labelled button and testing is conducted accurately and quickly.

A range of useful accessories are supplied alongside the Kewtech EZYPAT. These include an extension lead adaptor, test probe, test lead, crocodile clip and carry case. The small size and low weight of the tester mean it is easy to transport around large sites so it is ideal for caretakers and other responsible members of staff in environments such as schools and large offices.

Kewtech part number: EZYPAT

Kewtech EZYPAT Features

  • Earth bond continuity (200mA)
  • Quick and 5s continuity test
  • Insulation test (250V or 500V test voltage)
  • Substitute leakage current
  • Test lead resistance nulling
  • Auto-test sequences
  • Backlit LCD screen
  • Green = PASS, red = FAIL
  • Battery operated

 

EZYPAT EZYPAT Plus SMARTPAT
200mA continuity test
250V Insulation Test
500V Insulation Test
Substitute Leakage Measurement
Polarity Check
110V Load and Run Test
230V Load and Run Test
Portable RCD Test
Compatible with KEWPAT App
Customisable Test Sequences

Specification

Protective Conductor Resistance

  • Measuring range: 0.00 – 20.00 Ω (NULL value inc)*
  • Over-range indication: > 20.00 Ω
  • Resolution: 0.01Ω
  • Open-circuit voltage: 5 V ±0.4 V DC
  • Measuring current: 200 mA DC (nominal value)
  • Accuracy: ±3%rdg ±5dgt

Insulation

  • Rated voltage: 250V / 500V
  • Measuring range: 0.00 – 20.00 MΩ
  • Over-range indication: > 20.00 MΩ
  • Resolution: 0.01 MΩ
  • No-load voltage: 250 V DC +20%, -0% / 500 V DC +20%, -0%
  • Short-circuit current: 1.5 mA DC or less
  • Rated current: 1 -1.2 mA with a load of 0.25 MΩ / 1 to 1.2 mA with a load of 0.5 MΩ
  • Accuracy: ±2%rdg±3dgt

Substitute Leakage

  • Measuring range: 0.10 – 12.00 mA rms
  • Over-range indication: > 12.00 mA
  • Resolution: 0.01mA
  • Open-circuit voltage/ Freq.: 30 V ±5 V rms / 50 Hz ±5%
  • Measuring current: 1.2 mA AC ±0.5 mA (when measuring 12.00 mA)
  • Accuracy: ±3%rdg±5dgt

Applicable Standards

  • Safety: IEC/EN61010-1 CAT II 300V-instrument; IEC/EN61010-2-030; IEC/EN61010-031 CAT III 600V
  • EMC: EN61326-1, 2-2
  • Possible number of measurements where battery voltage is within the effective range (measuring every 30 sec): Approx. 1400 times (CLI Rpe: 0 Ω, Rins: 1.1 MΩ)

Supplied Accessories

  • Kewtech EZYPAT PAT Tester
  • Earth lead with probe and croc clip
  • Extension lead adapter
  • Carry bag with strap
  • Quickstart manual
  • End of line Cal Cert