  • Onboard internal memory for up to 200 test results
  • Provides user-adjustable PASS/FAIL limits
  • Dual voltage insulation test and low current earth bond test

Free gift

Includes: 110V appliance adaptor, 500 PASS labels, 200 FAIL labels, 250 Passwrap labels, IEC cloverleaf adaptor, and PAT register book.

Optional Extras

£348.00+VAT
In stock
+

Free gift with this product

Martindale Accessory Bundle
Martindale PAT Accessory Kit
Worth £85.00

Includes: 110V appliance adaptor, 500 PASS labels, 200 FAIL labels, 250 Passwrap labels, IEC cloverleaf adaptor, and PAT register book.

Product videos

Description

The Martindale HPAT600/2 PAT Tester is lightweight, portable instrument that offers reliable standard testing alongside test result storage, and a dual-voltage insulation test. It is suitable for appliance testing in residential and commercial settings.

The Martindale HPAT600/2 has a manual mode whereby earth bond testing and 250V/500V insulation testing are triggered using individual buttons whilst an automatic mode has pre-set test sequences for Class I and Class II appliances as well as extension leads.

Up to 200 test results can be saved to the Martindale HPAT600/2’s internal memory and the user can recall these results to the screen. The operator can set their own pass limits which can come in useful when testing long extension leads.

Key Features

  • Manual and automatic testing modes
  • Internal memory for 200 results
  • Insulation testing at 250V and 500V
  • Low current 200mA earth bond test
  • PASS/FAIL indication alongside test value

Specification

Earth Continuity

  • Test Voltage: 4V DC (into open circuit)
  • Test Current: 200mA DC (into short circuit)
  • Range: 0 – 19.99Ω
  • Resolution: 0.01Ω
  • Accuracy: ± (5% reading + 2 digits)
  • Default PASS Levels (Class I) 0.1 Ω.
  • Default PASS Levels (Lead) 0.1 Ω
  • User Selectable Pass Levels 0.1Ω to 0.9Ω in 0.1Ω steps

Insulation

  • Test Voltage (500V Range) >500V DC at 1mA ( < 600V DC into open circuit)
  • Test Voltage (250V Range) >250V DC at 1mA ( < 300V DC into open circuit)
  • Test Current 1.5mA (into short circuit)
  • Ranges 2.00MΩ, 20.0MΩ, 200MΩ
  • Resolution 0.01MΩ
  • Accuracy: ± (5% reading + 2 digits)
  • Default Pass Level (Lead): 1 MΩ
  • Default Pass Level (Class I): 1 MΩ
  • Default Pass Level (Class II): 2 MΩ
  • User Selectable Pass Levels: 0.3 MΩ to 1MΩ in 0.1MΩ steps; 1MΩ to 10MΩ in 1MΩ steps

Fuse Test

  • Test Voltage: 4V DC (into open circuit)
  • Test Current: 200mA DC (into short circuit)
  • Pass Level: >2mA

Simulated Load Test

  • Test Voltage: 4V DC (into open circuit)
  • Test Current: 200mA DC (into short circuit)
  • Accuracy: ± (5% reading + 2 digits) (referenced to 230V)

General

  • Overload Protection: 300V AC/DC
  • Protection Class: IP20
  • Safety: Complies to BS EN 61010-1:2001
  • Temperature Range: -10 to 40°C, non-condensing
  • Power Supply 6 x 1.2V AA NiMH rechargeable batteries 1800mAh, or greater
  • Dimensions: 90 x 210 x 54mm
  • Weight: Approx 700g (including batteries and leads)

Supplied Accessories

The Martindale HPAT600/2 comes with:

  • Test Lead with crocodile clip
  • Mains Lead and In-Car Charger
  • Instruction Manual
  • 12 Month Warranty
  • 6 x AA Rechargeable Batteries