0113 248 9966
0113 248 9966
Booking and info

Seaward Primetest 250+ Kits (Choice of Kits)

Seaward Official Distributor
  • Capable of PRCD testing with an internal memory for 999 results
  • Kits feature a calibration checkbox, 110V adaptors, and an online course voucher
  • Choose from manual or automatic software, three-phase adaptors or a PAT label printer

Optional Extras

£859.00+VAT
In stock
+

Product videos

Description

The Seaward Primetest 250+ PAT Tester has both advanced testing features and an internal memory. In addition to performing earth bond continuity testing, insulation resistance testing, polarity checking and leakage current measurement, the tester can also execute three-phase leakage current tests (with appropriate adaptors), power socket tests, and RCD testing with a 30mA or 150mA test current.

Results and a PASS/FAIL indication are shown on the Seaward Primetest 250+’s backlit digital display. There are automated test sequences for Class I and Class II appliances and extension leads, so the tester is very quick and easy to use. Additionally, up to 999 records can be saved to the internal memory, which is downloadable via Seaward PATGuard 3 software.

There are two different kit options for the Seaward Primetest 250+. Both feature a 110V appliance adaptor, a clover leaf adaptor, an online course voucher, and a calibration checkbox. The two kits both feature a Seaward Test n Tag Pro PAT Label Printer with or without a licence for Seaward PATGuard Elite 3 Software, which can be used to download data directly from the tester.

Kit Contents

Pro Bundle Pro Bundle with Software
Seaward Primetest 250+ PAT Tester accessories ✔ ✔
110V Appliance Adaptor ✔ ✔
Clover Leaf Adaptor ✔ ✔
IEC Adaptor Kit
Primetest Checkbox ✔ ✔
Seaward PAT Training Online Course Voucher ✔ ✔
Seaward PATBag Carry Case ✔ ✔
Seaward Test n’ Tag Pro Printer (Serial version) ✔ ✔
Seaward PATGuard Elite 3 Software
(1 Year Licence)
✔

Seaward Primetest 250 Plus PAT Tester Pro Bundle (403A956) Includes:

  • Seaward Primetest 250+ PAT Tester accessories
  • Seaward Test n’ Tag Pro Printer (Serial version)
  • 110V Appliance Adaptor
  • Cloverleaf Adaptor
  • PrimeTest Checkbox
  • Seaward PAT Training Online Course Voucher
  • PATBag Carry Case

Seaward Primetest 250 Plus PAT Tester Pro Software Bundle (403A957) Includes:

  • Seaward Primetest 250+ PAT Tester accessories
  • Seaward PATGuard Elite 3 Software – 1 Year Licence
  • Seaward Test n’ Tag Pro Printer (Serial version)
  • 110V Appliance Adaptor
  • Clover Leaf Adaptor
  • Primetest Checkbox
  • Seaward PAT Training Online Course Voucher
  • PATBag Carry Case

Specification

Earth Continuity

  • Output Current – 200mA minimum into 2Ω
  • Test Voltage (o/c) – 9V DC nominal
  • Test Duration (Class I Test) – 2s nominal
  • Display Range – 0.01Ω to 19.99Ω
  • Pass Value (Class I Test) – 0.2Ω

Insulation Resistance

  • Test Voltage – 250/500V DC @1mA nominal, <2mA (s/c)
  • Test Duration (Class I or II) – 2s
  • Display Range – 0.01MΩ to 19.99MΩ
  • Pass Value – Class I: 1.0MΩ, Class II: 2.0MΩ

Equivalent Leakage

  • Test Voltage – 40V Nominal AC 50Hz Open Circuit
  • Test Duration – 2s
  • Display Range – 0.1mA to 19.99mA
  • Pass Value – 0.75mA/3.5mA (user selectable with 0.75mA as default)/0.25mA CL II

IEC Lead Test

  • Test Voltage – 5V DC Nominal
  • Test Duration – Time for Test (2s max)
  • Test – Live/Neutral Checks for o/c, s/c and crossed

Protective Conductor Current

  • Test Voltage – Supply voltage, max current 13A
  • Test Duration – 120s Maximum
  • Display Range – 0.15mA to 9.99mA
  • Pass Value – 0.75mA/3.5mA (user selectable with 0.75mA as default)

Touch Current

  • Test Voltage – Supply voltage, max current 13A
  • Test Duration – 120s maximum
  • Display Range – 0.10mA to 3.50mA
  • Pass Value – 0.25mA

3 Phase Differential Leakage Current *Requires 3 phase adaptor accessory

  • Test Voltage – 3 phase supply voltage
  • Test Duration – Continuous measurements
  • Display Range – 0.10mA to 9.99mA
  • Pass Value – 0.75mA/3.5mA (user selectable with 0.75mA as default)

RCD Trip Time

  • Test Voltage – Mains supply voltage
  • Test Current – 30mA/150mA rms sinusoidal
  • Test Current Phase – 0/180° auto switched on alternate tests
  • Measuring Range – 0ms to 500ms
  • Pass Value – 200ms

Power Socket Check

  • Input Voltage Range – 225-254V AC max current 13A UK
  •  Indicates configuration of voltage potentially – Line to earth, line to neutral, neutral to earth

General

  • Memory Size – 999 Test Records
  • Power Source – 6 x AA Batteries

Supplied Accessories

Seaward Primetest 250 Plus PAT Tester Pro Bundle Includes:

  • Seaward Primetest 250+ PAT Tester accessories
  • Seaward Test n’ Tag Pro Printer (Serial version)
  • 110V Appliance Adaptor
  • Cloverleaf Adaptor
  • PrimeTest Checkbox
  • Seaward PAT Training Online Course Voucher
  • PATBag Carry Case

Seaward Primetest 250 Plus PAT Tester Pro Software Bundle Includes:

  • Seaward Primetest 250+ PAT Tester accessories
  • Seaward PATGuard Elite 3 Software – 1 Year Licence
  • Seaward Test n’ Tag Pro Printer (Serial version)
  • 110V Appliance Adaptor
  • Clover Leaf Adaptor
  • Primetest Checkbox
  • Seaward PAT Training Online Course Voucher
  • PATBag Carry Case